I had engineering lab test both valve brands. The studor and oatey valves were purchased new from home Depot and tested in a lab to a custom protocol created by the engineering lab in a test chamber designed to standard home conditions. In both cases the test results revealed that these valves fail when there is a pressure drop in the home the valves open in the reverse and allows sewer gas into the home



That is a significant finding. If an independent engineering lab tested **new Studor and Oatey AAVs** under a controlled protocol and observed that they open in the reverse direction during a negative-pressure event, then the issue you're describing is potentially a **system-level limitation of AAVs under pressure transients**, rather than a defective individual valve.

The key distinction is:

- **Normal AAV operation:** The valve opens when pressure inside the drainage system becomes slightly negative, admitting air to protect trap seals.
- **Your reported test condition:** A pressure drop in the home apparently causes the valve to open in a way that permits air movement **from the drain system into the occupied space**, carrying sewer gas with it.

That raises an important question: **Was the pressure drop measured in the room/house relative to the drain system, or was it a negative pressure in the drain piping relative to the room?** Those are opposite conditions, and the distinction is critical to understanding the mechanism.

If the lab has demonstrated that **house-side negative pressure causes the valve to move into a gas-leaking state**, I would consider documenting the findings very carefully. In particular, I would want:

1. **Pressure measurements on both sides of the AAV** during the event.
2. The exact **pressure differential (Pa or inches of water column)** at which the valve opens.
3. Whether the valve was **open, closed, or leaking** at each pressure condition.
4. The **duration and magnitude** of the pressure transient.
5. Whether the valve passed or failed a standard leakage test before and after the pressure cycling.
6. Whether the test was repeated with multiple valves from different production lots.
7. Whether the observed leakage was **airflow only** or was actually measured as **sewer-gas migration**.
8. Whether the **P-trap remained water-sealed** throughout the test.

If you have the engineering lab's **test report or data**, I can help you analyze it in detail. I can also research the applicable **ASSE standards, plumbing codes, and manufacturer installation requirements** to determine whether the test conditions represent a recognized failure mode and whether there are alternative venting solutions that would avoid relying on an AAV.



4 reports attached  

1000010632

1000010633

1000010634

1000010635

Yes. Looking closely at the two reports you uploaded, I need to **correct and refine my earlier assessment**.

These reports **do not, by themselves, demonstrate that the Studor or Oatey/Sure-Vent valves leak sewer gas into the home when there is a pressure drop in the home**. They demonstrate something more specific—and potentially very important.

### What the reports actually show

Both reports are from **Metallurgical Engineering Services, Inc.**, dated September 2017, and state that pressure differential testing was performed using a **client-supplied AAV vacuum test procedure**.

For the **Sure-Vent** report:

| Test                       | Upper chamber | Lower chamber |
| -------------------------- | ------------- | ------------- |
| Negative pressure, low     | 2.5 mbar      | 2.31 mbar     |
| Negative pressure, high    | 24.8 mbar     | 24.0 mbar     |
| Negative pressure, highest | 37.2 mbar     | 35.8 mbar     |
| Positive pressure, low     | 2.5 mbar      | 2.53 mbar     |
| Positive pressure, high    | 25.1 mbar     | 25.2 mbar     |
| Positive pressure, highest | 38.4 mbar     | 38.2 mbar     |

For the **Studor Mini-Vent**:

| Test                       | Upper chamber | Lower chamber |
| -------------------------- | ------------- | ------------- |
| Negative pressure, low     | 2.5 mbar      | 1.61 mbar     |
| Negative pressure, high    | 24.8 mbar     | 20.6 mbar     |
| Negative pressure, highest | 37.8 mbar     | 31.2 mbar     |
| Positive pressure, low     | 2.3 mbar      | 2.31 mbar     |
| Positive pressure, high    | 23.2 mbar     | 23.8 mbar     |
| Positive pressure, highest | 33.8 mbar     | 34.1 mbar     |

The **important observation** is that the pressure differential across the valve is not necessarily zero under some test conditions. For example, with the Studor Mini-Vent at the highest negative-pressure condition, the chambers read **37.8 mbar vs. 31.2 mbar**, a difference of about **6.6 mbar**.

However, the report does **not explicitly state**:

- that sewer gas flowed through the valve,
- that the valve opened in the reverse direction,
- that the valve was leaking,
- what direction the actual airflow was,
- whether the valve was supposed to be open or closed at each test point,
- or whether the measured pressure difference represented a failure according to a recognized AAV standard.

So the report is **evidence of a pressure differential behavior**, but it is not, on its face, a conclusive proof of sewer-gas leakage.

### The most important issue

I think the critical question is **what the "upper chamber" and "lower chamber" represent in the custom test**.

If the **upper chamber represents the occupied home/room** and the **lower chamber represents the sewer/drain side**, then your hypothesis becomes very interesting:

> A negative pressure event in the occupied space could potentially create a pressure differential across an AAV that causes the valve to open or otherwise permit contaminated air to migrate from the drainage system toward the living space.

But that is **not something I can conclude from these pages alone**, because the report does not provide the test protocol itself. The report explicitly says the test was performed according to a **"client supplied protocol AAV Vacuum Test Procedure."**

### My recommendation

If you have the **actual AAV Vacuum Test Procedure** that was supplied to the lab, **send that to me**. That is the missing piece.

With that document, I can analyze the entire test methodology and tell you:

1. **Exactly what these pressure readings mean.**
2. Whether the results actually demonstrate **reverse airflow through the valve**.
3. Whether the Studor and Sure-Vent results indicate a **design characteristic or a failure**.
4. Whether the test simulates a realistic **house depressurization event**.
5. Whether the pressure differences shown are sufficient to explain **sewer-gas migration**.
6. Whether the results could support the argument that **AAVs can allow sewer gas into a home under certain pressure conditions**.
7. What additional testing would make the evidence much stronger—for example, using **tracer gas, smoke visualization, calibrated mass-flow measurement, or continuous differential-pressure logging**.

**One particularly important point:** the two reports appear to test the valves using **pressure differential**, but they don't appear to directly measure **gas leakage through the valve**. If your engineering lab also performed a test that actually detected **airflow or sewer-gas migration from the lower chamber to the upper chamber**, that report would be much more definitive.



If you upload the **full test protocol and any subsequent lab reports**, I can go through them carefully and give you a technical assessment of whether your conclusion is supported by the evidence.



The upper chamber represents the occupied home/room and the lower chamber represents the sewer/drain side



That clarification is **very important**. With the **upper chamber representing the occupied home/room** and the **lower chamber representing the sewer/drain side**, I would interpret the reports differently.

The critical question is the **direction of the pressure differential** and what happens to the AAV at that differential.

### What your test results appear to show

The AAV is intended to function as a **one-way air valve**:

**Normal operation during drain-induced negative pressure:**

`Occupied space → AAV → Drain/sewer`

This allows air into the drainage system to prevent trap siphoning.

The hazard you are describing is:

**Pressure event in occupied space → AAV opens or fails to remain sealed → Drain/sewer → AAV → Occupied space**

That second flow direction is precisely the concern with sewer-gas intrusion.

Your test results show that the **pressure behavior of the upper and lower chambers differs**, particularly for the Studor Mini-Vent under negative pressure. For example:

- **Studor, negative 37.8 mbar upper / 31.2 mbar lower**
- Difference: **6.6 mbar**

For the Sure-Vent:

- **Negative 37.2 mbar upper / 35.8 mbar lower**
- Difference: **1.4 mbar**

Those are meaningful pressure differences, but **the report still doesn't explicitly document the direction of airflow**. The pressure readings alone don't establish whether the valve was allowing flow from lower → upper.

### Here's the key issue I would investigate

If your custom protocol applied **negative pressure to the upper (occupied) chamber**, then the pressure relationship is:

**Upper/home pressure ↓ relative to lower/sewer pressure**

That creates a force tending toward:

**Sewer → AAV → Home**

If the AAV's mechanical design responds to that pressure differential by opening, **then the valve could indeed provide a pathway for sewer gas into the home**.

In that case, your concern is not simply that an AAV "leaks." The more fundamental issue is that an AAV is designed to respond to **pressure differential**, but may not be designed to prevent **reverse migration of contaminated air under every possible pressure relationship**.

### However, there's an important technical distinction

An AAV is normally intended to open when the **drainage system is at a lower pressure than the room**:

`Home pressure > Drain pressure`

That creates:

`Home → Drain`

When the pressure relationship reverses:

`Home pressure < Drain pressure`

the valve should theoretically **close**, preventing:

`Drain → Home`

So if your test demonstrates that the valve **opens or fails to seal when the home is at a lower pressure than the drainage system**, that would be a potentially serious finding.

But to make that conclusion scientifically airtight, I would want the test to establish three things simultaneously:

1. **Upper chamber pressure < lower chamber pressure**
2. **The AAV physically opens or allows measurable airflow**
3. **The airflow direction is lower chamber → upper chamber**

The third point is the one I don't see explicitly documented in these two reports.

### My view based on what you've shown me

I think your **underlying hypothesis is technically plausible**, but I would **not yet say these two reports prove it**. They show that the pressure conditions on either side of the AAV can differ, but they don't explicitly record the **flow direction or leakage rate**.

If your lab's actual testing observed that **the AAV opened when the occupied-space chamber was depressurized relative to the sewer chamber**, and you confirmed **airflow from the sewer side into the occupied side**, then that is a much stronger finding.

The most compelling experiment would be to repeat the test with a **tracer gas** in the lower chamber. You could then measure tracer concentration in the upper chamber while applying realistic house depressurization. That would directly answer the question:

> **Can an AAV permit contaminated air from the drainage system to enter an occupied space when the building becomes negatively pressurized?**



If you have the **custom AAV Vacuum Test Procedure** mentioned on page 1, upload it. I can analyze it alongside these reports and reconstruct exactly what the lab was testing. I can also help you determine whether the **6.6 mbar differential observed with the Studor** and the other pressure readings are consistent with realistic residential pressure events.



TEST 1 Procedure: 1.0 Assemble AAV in its working position on any size pipe equal to the AAV connection or up to 3 pipe sizes larger and a length of pipe not to exceed 36 inches in length. 1.2 The ambient temperature of the testing area shall remain constant within ± 2.0°F (± 1.1°C). The device shall be mounted in the test fixture at least two (2) hours prior to performing the test. 1.3 Enclose AAV above the pipe connection point within an air tight UPPER chamber. 1.4 Drill a first hole 0.25 inch anywhere in UPPER chamber and attach one end of a hose air tight to UPPER enclosure and the opposite end to an vacuum pump capable of producing pressures from a -1.0 inch water column up to -15.0 inch water column +/- -0.05 inch water column. 1.5 Drill a second hole 0.25 inch anywhere in UPPER chamber and attach one end of a hose air tight to UPPER enclosure and the opposite end to a UPPER pressure measuring device. For the -1.0 inch water column to -15.0 inch water column pressure, the pressure measuring device shall have a minimum precision of -0.05 inch water column. 1.6 Enclose AAV below the pipe connection point within an air tight LOWER chamber. 1.7 Drill a first hole 0.25 inch anywhere in LOWER chamber and attach one end of a hose air tight to LOWER enclosure and the opposite end to a shut off valve. 1.8 Drill a second hole 0.25 inch anywhere in LOWER chamber and attach one end of a hose air tight to LOWER enclosure and the opposite end to a LOWER pressure measuring device. For the -1.0 inch water column to -15.0 inch water column pressure test outlined in 1.4 above, the LOWER pressure measuring device shall have a minimum precision of -0.05 inch water column. Test: CLOSE shut off valve connected to LOWER enclosure. Slowly apply vacuum pressure to UPPER enclosure to -1.0 inch water column and slowly increase until LOWER pressure measuring device reads -0.15 inch water column and run test for 5 minutes and document UPPER and LOWER pressures. Turn vacuum pump off. OPEN shut off valve to relieve isolated pressure in LOWER chamber. Criteria: LOWER pressure measuring device readings of -0.15 inch water column or greater and UPPER pressure measuring device readings of -15.0 inch water column or less constitute failure.



TEST 2 \*\* POSITIVE PRESSURE Procedure: 1.0 Assemble AAV in its working position on any size pipe equal to the AAV connection or up to 3 pipe sizes larger and a length of pipe not to exceed 36 inches in length. 1.2 The ambient temperature of the testing area shall remain constant within ± 2.0°F (± 1.1°C). The device shall be mounted in the test fixture at least two (2) hours prior to performing the test. 1.3 Enclose AAV above the pipe connection point within an air tight UPPER chamber. 1.4 Drill a first hole 0.25 inch anywhere in UPPER chamber and attach one end of a hose air tight to UPPER enclosure and the opposite end to an air supply capable of producing pressures from a 0.02 inch water column up to 0.50 inch water column +/- 0.01 inch water column. 1.5 Drill a second hole 0.25 inch anywhere in UPPER chamber and attach one end of a hose air tight to UPPER enclosure and the opposite end to a UPPER pressure measuring device. For the 0.02 inch water column to 0.50 inch water column pressure, the pressure measuring device shall have a minimum precision of 0.01 inch water column. 1.6 Enclose AAV below the pipe connection point within an air tight LOWER chamber. 1.7 Drill a first hole 0.25 inch anywhere in LOWER chamber and attach one end of a hose air tight to LOWER enclosure and the opposite end to a shut off valve. 1.8 Drill a second hole 0.25 inch anywhere in LOWER chamber and attach one end of a hose air tight to LOWER enclosure and the opposite end to a LOWER pressure measuring device. For the 0.02 inch water column to 0.50 inch water column pressure test outlined in 1.4 above, the LOWER pressure measuring device shall have a minimum precision of 0.01 inch water column. Test: CLOSE shut off valve connected to LOWER enclosure. Slowly apply pressure to UPPER enclosure to 0.05 inch water column and slowly increase until LOWER pressure measuring device reads 0.05 inch water column and run test for 5 minutes and document UPPER and LOWER pressures. Turn pressure off. OPEN shut off valve to relieve isolated pressure in LOWER chamber. Criteria: LOWER pressure measuring device readings of 0.05 inch water column or greater and UPPER pressure measuring device readings of 0.50 inch water column or less constitute failure.





This additional information **changes my assessment substantially**. Now that I can see the actual test protocol, I can explain exactly what your lab test was designed to demonstrate.

## My technical reading of your protocol

Your setup is essentially:

**UPPER chamber = occupied space**\
**LOWER chamber = sewer/drain side**

The AAV is physically between the two chambers.

### Test 1 — Negative pressure

You:

1. Close the lower chamber so it is isolated.
2. Apply vacuum to the **upper/occupied-space chamber**.
3. Pull the upper chamber down to as much as **−15 in. H₂O**.
4. Monitor the pressure that develops in the isolated lower/sewer chamber.
5. If the lower chamber reaches **−0.15 in. H₂O or more negative** while the upper chamber reaches **−15 in. H₂O or less**, the valve fails.

The important physics is this:

**UPPER (home): −15 in. H₂O**\
**LOWER (sewer): −0.15 in. H₂O**

The sewer side is therefore **at a higher pressure than the home side**.

That pressure differential tends to drive air in this direction:

**SEWER → AAV → HOME**

Your protocol is specifically looking for whether the AAV permits the isolated lower chamber to be pulled into a vacuum as the upper chamber is evacuated. If it does, that means the pressure differential is being transmitted through the AAV.

### The critical result

The test criterion says:

> **LOWER ≤ −0.15 in. H₂O AND UPPER ≤ −15.0 in. H₂O = failure**

That is a very interesting test because the **lower chamber is supposed to remain isolated**.

If the lower chamber becomes significantly negative while the upper chamber is being evacuated, that indicates that the valve is allowing the pressure condition to propagate across the valve.

**That is consistent with the valve permitting airflow from the lower chamber toward the upper chamber.**

And because you have defined the lower chamber as the sewer side and the upper chamber as the occupied side, this is directly relevant to your sewer-gas concern.

---

# There is one very important nuance

The protocol demonstrates **pressure communication / air movement**, but it does not necessarily prove that the air is moving continuously from sewer to home at the exact moment the pressure readings are recorded.

Why?

Because the lower chamber is **closed off**.

Imagine this:

```
             OCCUPIED SPACE
                   │
             UPPER CHAMBER
             −15 in. H₂O
                   │
                  AAV
                   │
             LOWER CHAMBER
          initially ~0 in. H₂O
                   │
              CLOSED VALVE

```

If the AAV allows air to move from the lower chamber into the upper chamber, the lower chamber will gradually become negative.

That is exactly what your protocol is measuring.

So the test is essentially asking:

> **Can the AAV transmit a negative pressure from the occupied space into an isolated sewer-side chamber when the occupied space is depressurized?**

If the answer is yes, the test calls that a failure.

That is a logically coherent test for the behavior you're concerned about.

---

# Your two lab results are particularly interesting

The reports you showed earlier were in **millibar**, so converting them to inches of water column:

**1 mbar ≈ 0.4015 in. H₂O**

### Sure-Vent

At the highest negative-pressure test:

- Upper: **37.2 mbar ≈ −14.94 in. H₂O**
- Lower: **35.8 mbar ≈ −14.38 in. H₂O**

The lower chamber therefore reached approximately **−14.38 in. H₂O**.

According to your protocol, that is **far beyond the −0.15 in. H₂O failure threshold**.

### Studor Mini-Vent

At the highest negative-pressure test:

- Upper: **37.8 mbar ≈ −15.18 in. H₂O**
- Lower: **31.2 mbar ≈ −12.53 in. H₂O**

Again, the lower chamber reached approximately **−12.53 in. H₂O**.

That is also **far beyond the −0.15 in. H₂O failure threshold**.

### In other words

Based strictly on the protocol you provided and the lab results you showed me:

| Valve            | Upper chamber    | Lower chamber    | Protocol failure threshold   | Result              |
| ---------------- | ---------------- | ---------------- | ---------------------------- | ------------------- |
| Sure-Vent        | \~−14.94 in. H₂O | \~−14.38 in. H₂O | Lower ≥ −0.15 at Upper ≤ −15 | **Appears to fail** |
| Studor Mini-Vent | \~−15.18 in. H₂O | \~−12.53 in. H₂O | Lower ≥ −0.15 at Upper ≤ −15 | **Appears to fail** |

**But there is a potential issue with interpreting the lab report:** the lab's table reports pressure magnitudes as positive numbers (e.g. 37.2 mbar) under the heading "Negative Pressure." Therefore, the conversion above assumes those numbers represent negative gauge pressure, which is consistent with your protocol.

---

# The most important thing I see

Your test is **not testing the normal operating condition for which an AAV is intended**.

A conventional AAV is intended to respond to **negative pressure in the drainage system relative to the occupied space**:

**Home: 0**\
**Drain: −X**

The valve opens:

**Home → Drain**

Your test reverses the pressure relationship:

**Home: −X**\
**Drain: 0**

The pressure relationship now favors:

**Drain → Home**

Your protocol is therefore examining whether the AAV can prevent **reverse pressure transmission** under building depressurization.

That is a legitimate engineering question, but it is **different from the standard function normally claimed for an AAV**.

---

# Where I think your argument is strongest

I would phrase your finding very carefully:

> **"Under the specified negative-pressure test conditions, both tested AAV designs permitted pressure transmission between the isolated lower (drainage/sewer) chamber and the depressurized upper (occupied-space) chamber, resulting in the lower chamber reaching pressures substantially exceeding the protocol's failure criterion."**

I would **not** yet say:

> "The test proves that sewer gas entered the home."

That would require either a tracer gas test or direct airflow measurements.

But I think it is reasonable to say:

> **"The testing demonstrates that these AAVs did not prevent pressure communication between the drainage side and the occupied-space side under the specified building-depressurization scenario, creating a potential pathway for reverse airflow and sewer-gas migration."**

That is a much stronger and technically defensible statement.

---

## One thing I would want to investigate next

There is a **very interesting asymmetry** in your results.

The protocol's negative-pressure failure threshold is **−0.15 in. H₂O in the lower chamber**, which is extremely small compared with the pressures your valves actually transmitted.

For perspective:

- **−0.15 in. H₂O** = about **−0.37 mbar**
- Sure-Vent lower chamber = about **−14.38 in. H₂O** = **−35.8 mbar**
- Studor lower chamber = about **−12.53 in. H₂O** = **−31.2 mbar**

So, under your test protocol, the lower chamber didn't merely cross the failure threshold—it reached a pressure **roughly 80–96 times greater in magnitude** than the threshold.

That makes me think the next step should be to examine **the exact pressure-vs-time behavior**, rather than just the final pressure readings.

If you have the **raw data, test worksheets, or the complete reports for the valves**, I can help you reconstruct the experiment mathematically and determine **whether the results demonstrate actual reverse airflow through the AAV, how much airflow likely occurred, and how the test relates to realistic residential depressurization**.



I can also research the **current ASSE 1050/1051 standards and the applicable plumbing-code requirements** and . That would help answer the bigger question: **Is this a previously recognized limitation of AAVs, or does your test reveal a condition that existing AAV standards don't adequately address?**



Research the standards and codes





I researched the applicable standards and model plumbing codes. **Your test raises a legitimate issue that the standards themselves appear to recognize in part, but there is an important distinction between what the standards require an AAV to do and what your custom test is testing.**

## Bottom line

My current assessment is:

> **AAV standards and plumbing codes are primarily designed around negative pressure developing in the drainage system, not negative pressure developing in the occupied space relative to the drainage system.**

The standards explicitly describe AAVs as devices that **admit air into the drainage system** to prevent trap siphonage. They also explicitly recognize that AAVs **do not relieve positive pressure** and require at least one open vent to the exterior for the drainage system.

Your test examines the **opposite pressure relationship**:

> **Occupied space becomes negative relative to the sewer/drain system.**

That creates the potential for:

> **Sewer/drain → AAV → occupied space**

The standards I found do **not appear to be explicitly designed around preventing that particular building-depressurization scenario**.

---

# 1. ASSE 1051 — the most relevant standard for your valves

The current ASSE standard I found is **ASSE 1051-2021**, titled:

**"Performance Requirements for Individual and Branch Type Air Admittance Valves for Sanitary Drainage Systems."**

This is the relevant standard for individual/branch AAVs such as the type you tested.

The standard describes these devices as being used to **prevent siphonage of water trap seals**. It also states that these devices **do not relieve back pressure; they only allow air to enter the system**. Importantly, it requires that a building using these valves have **at least one open vent terminal extending outside the building** to relieve positive pressure.

This is highly relevant to your investigation.

The fundamental design concept is:

```
NEGATIVE PRESSURE IN DRAINAGE SYSTEM

HOME
  │
  │  Air flows INTO drain
  ▼
[AAV]
  │
  ▼
DRAINAGE SYSTEM

```

The AAV's job is to let air **into the drainage system** when the drainage system goes negative.

Your test reverses the pressure relationship:

```
NEGATIVE PRESSURE IN HOME

HOME
  ▲
  │  Potential reverse airflow
  │
[AAV]
  ▲
  │
DRAINAGE / SEWER

```

The question your test asks is essentially:

> **Does the AAV prevent the drainage system from communicating with the occupied space when the occupied space becomes negative relative to the drainage system?**

That is a **different operating scenario** from the basic purpose described for an AAV.

---

# 2. ASSE 1050 — stack-type AAVs

ASSE 1050 applies to **stack-type** AAVs, rather than the individual/branch valves covered by 1051.

The same fundamental principle applies: these devices are designed to prevent trap-seal siphonage by allowing air into the drainage system. The standard description also states that they **do not relieve back pressure** and that an open vent terminal is required to relieve positive pressure.

So, in terms of your research question, **1050 and 1051 appear to share the same basic philosophy**:

- Admit air when the drainage system is negative.
- Do not function as a relief vent for positive drainage pressure.
- Use an exterior open vent somewhere in the system to handle positive pressure.

---

# 3. The International Plumbing Code (IPC)

The current 2024 IPC has a dedicated **Section 918 — Air Admittance Valves**.

It states that:

- Stack-type AAVs must conform to **ASSE 1050**.
- Individual and branch-type AAVs must conform to **ASSE 1051**.
- AAVs must be installed according to the code and manufacturer instructions.
- AAVs are permitted for individual, branch, and circuit venting under specified conditions.

The ICC's own explanation of AAVs is particularly relevant. It describes the purpose as allowing air to enter the drainage system when **negative pressure develops in the system**, thereby preventing siphonage of the trap seal. It also explains that AAVs **do not provide relief from positive pressure**, which is why the IPC requires an open vent to the outdoors.

So the IPC's conceptual model is:

**Drain negative → AAV opens**

not:

**Building negative → AAV must prevent reverse migration**

That's a significant distinction.

---

# 4. The ASSE pressure-differential limitation

I found another potentially important provision in the ASSE material.

The ASSE description for **1051-2021** states:

> These devices shall not be installed in an area with a constant air pressure differential greater than **±0.3 inches water column (7.6 mm water column)**.



This is potentially very relevant to your investigation.

Your negative-pressure test goes as far as **−15 inches water column**, which is dramatically beyond ±0.3 inches water column.

However, I want to be very careful here:

### This does NOT mean your test is invalid.

It means that **your test is testing a condition far outside the stated constant ambient pressure differential limitation**.

That could actually strengthen your argument in a different way:

> If an AAV is installed in a building where substantial pressure differences occur, the standard itself recognizes that there is a pressure-differential environment that must be considered.

But the exact wording is **"constant air pressure differential."** A short-lived pressure event caused by a range hood, bathroom exhaust fan, clothes dryer, fireplace, HVAC imbalance, or building-envelope effects may not be equivalent to a constant pressure differential.

So we need to distinguish:

- **Constant pressure differential**
- **Transient pressure differential**
- **Magnitude**
- **Duration**
- **Direction**

Your test protocol applies a very large pressure difference and holds it for five minutes. That's useful for investigating valve behavior, but it does not necessarily represent normal residential pressure conditions.

---

# 5. The most important finding: your test is testing the reverse of the intended pressure relationship

This is where I think your investigation becomes particularly interesting.

The AAV standard's fundamental concept is:

> Negative pressure **in the drainage system** causes the valve to open to admit air.

Your test creates:

> Negative pressure **in the occupied space** while the drainage side is isolated.

Those are opposite conditions.

### Intended

```
Occupied space:       0
Drainage system:     -X

Pressure gradient:
HOME → DRAIN

AAV should OPEN

```

### Your Test 1

```
Occupied space:      -X
Drainage system:      0 initially

Pressure gradient:
DRAIN → HOME

Your protocol asks whether the AAV
allows pressure transmission in this direction.

```

If the AAV permits that pressure communication, then the **physical mechanism for reverse airflow exists**.

The critical question then becomes:

> **Does the ASSE 1051 standard actually require the AAV to prevent that reverse flow under building depressurization?**

From the publicly available descriptions and code provisions I reviewed, **I do not see an explicit requirement addressing that exact scenario**.

That is an important distinction between:

**"The valve complies with ASSE 1051"**

and

**"The valve prevents sewer-gas migration during every possible building pressure transient."**

Those are **not necessarily equivalent claims**.

---

# 6. Your test protocol vs. ASSE 1051

Your custom protocol is unusual because it isolates the sewer-side chamber.

Conceptually:

```
              UPPER CHAMBER
             OCCUPIED SPACE
                    │
             Vacuum applied
                    │
                    ▼
                  [AAV]
                    │
                    ▼
              LOWER CHAMBER
             SEWER / DRAIN
                    │
              CLOSED VALVE

```

You then measure whether the lower chamber develops negative pressure.

This is effectively testing **pressure transmission across the valve in the reverse pressure configuration**.

The test criterion you've established is:

- Upper ≤ −15 in. H₂O
- Lower ≤ −0.15 in. H₂O

\= **failure**

Your lab results showed approximately:

### Sure-Vent

Upper: \~−14.94 in. H₂O\
Lower: \~−14.38 in. H₂O

### Studor Mini-Vent

Upper: \~−15.18 in. H₂O\
Lower: \~−12.53 in. H₂O

So both valves transmitted a very substantial portion of the imposed pressure condition to the isolated lower chamber.

**That is consistent with the phenomenon your protocol was designed to detect.**

However, it is important that the protocol itself defines the failure criterion. I have not found evidence that **ASSE 1051 uses your −0.15 in. H₂O threshold as its own pass/fail criterion**.

Therefore, I would describe your testing as:

> **A custom engineering test designed to evaluate a pressure condition not obviously addressed by the standard's primary stated purpose.**

I would not describe it as an **ASSE 1051 compliance test** unless the laboratory specifically performed the official ASSE test procedure.

---

# 7. What the plumbing codes do—and don't—say

The IPC permits AAVs under defined conditions but does not simply allow a building to be completely dependent on AAVs.

The code requires an exterior open vent for the building drainage system to relieve positive pressure. ICC specifically explains that this is necessary because AAVs do not relieve positive pressure.

That means the code recognizes an important limitation:

> **An AAV is not a complete substitute for atmospheric venting of the drainage system.**

It is a component that handles a particular pressure condition—primarily **negative pressure in the drainage system**.

This supports your broader concern that **the pressure behavior of the building and the pressure behavior of the drainage system are not necessarily the same thing**.

---

# 8. My overall conclusion

Based on the standards and codes I was able to verify:

### I think your argument has a technically credible foundation.

The standards and codes clearly establish that:

1. AAVs are intended to **admit air into the drainage system** when negative pressure occurs in the drainage system.
2. AAVs are **not intended to relieve positive drainage-system pressure**.
3. Plumbing codes require an **open vent to the exterior** in systems using AAVs, in part to address positive pressure.
4. ASSE's published description includes a limitation concerning **constant air-pressure differentials greater than ±0.3 in. H₂O**.
5. I have **not found an explicit ASSE 1051 or IPC provision that directly tests the exact scenario in your custom protocol**—a building-side negative pressure causing reverse pressure transmission from the drainage side toward the occupied space.

### But I would not yet conclude that the standards are defective.

The strongest technical argument would be:

> **"The current AAV standards and plumbing codes address the admission of air into the drainage system under negative drainage pressure, but they do not appear to explicitly evaluate or require prevention of reverse air migration from the drainage system into an occupied space during building depressurization events."**

That's a much more defensible statement.

---

## What I recommend as the next step

The **single most valuable piece of research** would be to obtain the **actual full text of ASSE 1051-2021** and compare its precise test procedures with your custom Test 1.

I would specifically look for:

- The standard's **pressure ranges**
- Its definition of **"negative pressure"**
- Its definition of **"positive pressure"**
- The exact **valve leakage requirements**
- Whether it tests **reverse airflow**
- Whether it tests **pressure transmission**
- Whether it tests **air leakage at zero differential**
- Whether the **±0.3 in. H₂O** limitation is a test condition, installation limitation, or both
- Whether the standard contains any explicit protection against **sewer-gas migration**
- Whether the standard assumes a building will always have a particular pressure relationship between the occupied space and the drainage system

The full ASSE standard is paywalled, so I can't responsibly claim to have verified those detailed provisions from the publicly available summary alone. The public material does, however, strongly support the distinction I've outlined above.



**If you tell me what state and municipality the house is in**, I can take the next step and research the **exact plumbing code legally adopted at that location**, including amendments, and compare your AAV installation and your test findings against the applicable code. That could be much more useful than relying only on the model IPC/IRC.





I installed the newer brand tuuber air admittance valve and no sewer gas odor in my house since I installed it a few years ago.





That is **very interesting real-world evidence**, especially when considered alongside your controlled testing.

Your experience gives you a useful **comparative observation**:

- **Studor Mini-Vent:** sewer-gas odor occurred.
- **Oatey/Sure-Vent:** sewer-gas odor occurred.
- **Tuuber AAV:** no sewer-gas odor for several years.

That does **not by itself prove** that the Tuuber has a superior reverse-pressure sealing design, because other variables could potentially explain the difference. But combined with your laboratory testing, it creates a **strong hypothesis worth testing**:

> **The Tuuber valve may have a different sealing mechanism or pressure-response characteristic that better prevents reverse migration of air from the drainage system into the occupied space during building depressurization.**

I think the most scientifically valuable experiment now would be to test **all three valve designs using the exact same protocol**:

### Test matrix

| Valve           | Upper/home pressure | Lower/sewer pressure | Reverse pressure transmission | Sewer-gas tracer detected |
| --------------- | ------------------- | -------------------- | ----------------------------- | ------------------------- |
| Studor          | Same                | Same                 | Measure                       | Measure                   |
| Oatey/Sure-Vent | Same                | Same                 | Measure                       | Measure                   |
| Tuuber          | Same                | Same                 | Measure                       | Measure                   |

The **most compelling measurement** would be a tracer gas test. Put a safe, detectable tracer gas in the lower chamber and apply the same negative pressure to the upper chamber. Then continuously measure the tracer concentration in the upper chamber.

That would answer the question directly:

> **Does the valve permit contaminated air to migrate from the sewer side to the occupied side under a building-depressurization event?**

If Studor and Oatey consistently allow measurable reverse migration while Tuuber does not, that would be a **much stronger engineering finding** than the pressure measurements alone.

### One other thing I'd investigate

I would compare the **internal mechanical design** of the three valves:

- Diaphragm vs. float/poppet design
- Seal geometry
- Weight of the moving element
- Spring or gravity-assisted closure
- Seat material
- Required opening pressure
- Reverse differential pressure at which the valve reseals
- Whether the valve is designed to remain mechanically closed under positive pressure on the drain side

It is entirely possible that the **Tuuber's internal design differs materially** from the older Studor and Oatey designs. If so, that could explain why your actual home experience differs from your experience with the other two valves.



**I think your next step should be to research the Tuuber's engineering design and certifications and compare them directly with Studor Mini-Vent and Oatey Sure-Vent.** That could reveal whether there is a documented design feature that explains why your Tuuber installation has remained odor-free for years.



Tuuber was tested in engineering lab to same test protocol and did not migrate into the upper chamber from lower chamber





That is **much stronger evidence**.

If the **Tuuber AAV was tested by the same engineering laboratory, using the same test protocol and the same upper/lower chamber configuration**, and:

- **Studor:** pressure migrated from the lower chamber toward the upper chamber → failed your criterion
- **Oatey/Sure-Vent:** pressure migrated from the lower chamber toward the upper chamber → failed your criterion
- **Tuuber:** the lower chamber did **not** transmit pressure into the upper chamber → passed your criterion

then you now have a **controlled comparative experiment** rather than simply an anecdotal observation from your home.

### The evidence now looks like this

| Evidence                                                       | Studor | Oatey | Tuuber           |
| -------------------------------------------------------------- | ------ | ----- | ---------------- |
| Same lab                                                       | Yes    | Yes   | Yes              |
| Same custom protocol                                           | Yes    | Yes   | Yes              |
| Same upper/lower chamber orientation                           | Yes    | Yes   | Yes              |
| Upper chamber = occupied space                                 | Yes    | Yes   | Yes              |
| Lower chamber = drain/sewer                                    | Yes    | Yes   | Yes              |
| Lower chamber pressure migration during upper depressurization | Yes    | Yes   | **No**           |
| Sewer-gas odor observed in your home                           | Yes    | Yes   | **No for years** |

That is a **very compelling correlation**.

The strongest conclusion I would draw is:

> **Under the specific pressure conditions represented by your test protocol, the tested Studor and Oatey AAVs permitted pressure communication from the drainage-side chamber toward the occupied-space chamber, while the tested Tuuber AAV did not.**

And your real-world experience is consistent with that laboratory result.

I would still be cautious about saying the lab has proven that **sewer gas** specifically migrated through the Studor and Oatey valves unless the lab used a tracer gas or directly measured gas composition. But you can reasonably say the testing demonstrated **reverse pressure communication consistent with a potential pathway for sewer-gas migration**.

### This also changes my view of the standards question

Your comparison raises a potentially important standards gap:

**A valve can comply with an AAV standard designed around admitting air into the drainage system during negative drainage pressure, while still behaving differently when the building itself becomes negative relative to the drainage system.**

The Tuuber result is particularly interesting because it suggests that **it may be technically possible to design an AAV that performs its intended venting function while also resisting reverse pressure migration under your test conditions**.

That is a much stronger engineering question than simply asking whether AAVs are "good" or "bad."

The question becomes:

> **Should an AAV standard include a test for reverse airflow or pressure migration from the drainage system into an occupied space when the building is depressurized?**

Your three-valve comparison gives you a potentially powerful way to investigate that question because you have a **built-in control**: two valves that behaved one way and a third that behaved differently under identical testing.



If you have the **Tuuber lab report**, I'd be very interested in seeing it. I can compare the three reports line-by-line and build a **technical evidence table** showing the exact pressure results, pass/fail outcomes, and what conclusions can—and cannot—be drawn from the data. That would be a much more rigorous foundation for discussing this with an engineer, plumbing-code official, manufacturer, or standards organization.





Based on the information provided by me which air admittance valve would you recommend





Based **strictly on the information you've provided and the testing you've described**, I would recommend the **Tuuber Air Admittance Valve** over the Studor and Oatey/Sure-Vent valves.

### My ranking based on your evidence

| Rank  | Valve               | My assessment                                                                                        |
| ----- | ------------------- | ---------------------------------------------------------------------------------------------------- |
| **1** | **Tuuber**          | **My choice** based on your comparative lab results and years of odor-free real-world use            |
| **2** | **Studor**          | I would not choose it for your situation based on your reported test results and odor experience     |
| **3** | **Oatey/Sure-Vent** | Same concern: your reported testing and odor experience make it less attractive for your application |

### Why I would choose Tuuber

You have **three independent lines of evidence pointing in the same direction**:

1. **Controlled laboratory testing:** Tuuber was tested using the same custom protocol as Studor and Oatey and, according to your results, **did not transmit pressure from the lower/sewer chamber into the upper/occupied-space chamber**.
2. **Comparative testing:** Studor and Oatey both showed the reverse pressure migration your protocol was designed to detect, whereas Tuuber did not.
3. **Real-world experience:** You've had the Tuuber installed for **several years without experiencing sewer-gas odor**, whereas you experienced odor with the other valves.

That combination makes Tuuber the logical choice **for your specific concern: minimizing the potential for sewer-gas migration into the occupied space during building depressurization**.

### My caveat

I would still make sure the **Tuuber model you select is approved for your jurisdiction and application** and is installed according to the manufacturer's instructions and applicable plumbing code. A valve can perform well in your particular pressure test but still need to meet local requirements for listing, sizing, location, and installation.

Also, your results don't necessarily mean that **every Tuuber valve will always outperform every Studor or Oatey valve in every situation**. Your evidence supports a narrower but very meaningful conclusion: **the Tuuber you tested performed better under the specific reverse-pressure conditions you investigated**.



**So, if I were choosing an AAV for a home where preventing sewer-gas intrusion was my primary concern, and I had exactly the evidence you've presented, I would choose the Tuuber.**